Specifications

1

1

0

1

4…20 mA

7.5 ms

5.0 ms

1

1

1

0

±10V

2.5 ms

2.5 ms

1

1

1

1

±5V

2.5 ms

2.5 ms

(1)

When IT = 1, the channel update rate for all channels is determined by the slowest channel.

Input Channel Configuration

03

02

01

00

Set these bits for channel 0

07

06

05

04

Set these bits for channel 1

11

10

09

08

Set these bits for channel 2

15

14

13

12

Set these bits for channel 3

Bit Settings

A/D Conversion Rate

Low Pass Filter

0

0

0

0

1200 Hz

No low pass

0

0

0

1

1200 Hz

100 ms low pass

0

0

1

0

1200 Hz

500 ms low pass

0

0

1

1

1200 Hz

1000 ms low pass

0

1

0

0

600 Hz

No low pass

0

1

0

1

600 Hz

100 ms low pass

0

1

1

0

600 Hz

500 ms low pass

0

1

1

1

600 Hz

1000 ms low pass

1

0

0

0

300 Hz

No low pass

1

0

0

1

300 Hz

100 ms low pass

1

0

1

0

300 Hz

500 ms low pass

1

0

1

1

300 Hz

1000 ms low pass

1

1

0

0

150 Hz

No low pass

1

1

0

1

150 Hz

100 ms low pass

1

1

1

0

150 Hz

500 ms low pass

1

1

1

1

150 Hz

1000 ms low pass

General

Attribute

Value

Module location

Cat. No. 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, 1794-TB3TS, and 1794-TBN

Number of inputs

4 isolated

Resolution

Voltage

Current

16 bits - unipolar; 15 bits plus sign - bipolar

0.156 mV/cnt unipolar; 0313 mV/cnt bipolar

0.320

μ

A

/

cnt unipolar;

0.640

μ

A

/

cnt bipolar

Update rate

2.5/5.0/7.5 ms all channels (see input update rate table)

Input current terminal

4…20 mA (user configurable)

0…20 mA (user configurable)

±20 mA (user configurable)

Input voltage terminal

±10V (user configurable)

0…10V (user configurable)

±5V (user configurable)

0…5V (user configurable)

Input Resistance

Voltage terminal

Current terminal

>10 M

Ω

<100

Ω

(3)

Data format

2’s complement

2’s complement %

binary

offset binary

Conversion type

Sigma Delta

Update rate

2.5/5.0/7.5 ms all channels (see input update rate table)

Normal mode rejection
ratio - voltage or current
Terminal

-3 dB @ 12 Hz (300 Hz conversion rate)

-80 dB @ 50 Hz (300 Hz conversion rate)

-3 dB @ 6 Hz (150 Hz conversion rate)

-80 dB @ 60 Hz (150 Hz conversion rate)

Common mode rejection
ratio

-120 dB @ 50/60 Hz

Step response to 63% -
voltage or current
terminal

1200 Hz conversion rate = 0.6 ms

600 Hz conversion rate = 06.7 ms

300 Hz conversion rate = 13.4 ms

150 Hz conversion rate = 26.7 ms

Absolute accuracy

(1)

voltage terminal

current terminal

0.1% Full Scale @ 25 °C

0.1% Full Scale @ 25 °C

Accuracy drift with
temperature

Voltage terminal

Current terminal

0.0028% Full Scale/°C

0.0038% Full Scale/°C

Calibration required

Factory calibrated. Can be calibrated in field when necessary

Maximum overload

30V continuous or 32 mA continuous, one channel at a time.

Indicators

1 red/green power/status indicator

Isolation voltage

120V (continuous), Basic Insulation Type, when used with 1794-TB2, 1794-TB3,
1794-TB3S, 1794-TB3T, or 1794-TB3TS

250V (continuous), Basic Insulation Type, when used with 1794-TBN

Type tested at 1500V AC for 60 s and Routine tested at 2550V DC for 1 s, between
channel to power, channel to system, and power to system, and channel to channel

Flexbus current

50 mA

Power dissipation

2.0 W maximum @ 31.2V DC

Thermal dissipation

Maximum 6.8 BTU/hr @ 31.2V DC

Keyswitch position

3

External DC Power
Supply voltage

Voltage range

Supply current

24V DC nominal

SUPPLY: 19.2-31.2V DC, 80 mA

FLEXBUS: 5V DC, 50 mA

Input: 0…20 mA, ±10V DC

Dimensions

46 mm x 94 mm x 75 mm (1.8 in. x 3.7 in. x 2.95 in.) with module installed in base

Wire size

Determined by installed terminal base

Wiring category

(2)

2 - on signal ports
2 - on power ports

Wire type

Shielded on signal ports

Enclosure type rating

None (open-style)

Terminal screw torque

Determined by installed terminal base

North American temp
code

T4

IEC temp code

T4

(1)

Includes offset, gain, nonlinearity and repeatability error terms.

(2)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1.

(3)

If 24V DC is removed from the module, input resistance = 10 k

Ω

Environmental

Attribute

Value

Operating
temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…70 °C (-4…158 °F)

Non-operating
temperature

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

General