16 DeviceNet 1732 ArmorBlock 16-Point I/O, Series A

Publication 1732D-IN002B-EN-E - January 2013

Refer to the device status indicator table for a description of the status indicators

Specifications

Device Status Indicators

Indicator

Status Description

Network status

Off

Device is not online:
- Device has not completed dup_MAC-id test.
- Device not powered – check module status
indicator.

Green

Device operating normally. As a Group 2 module, it
means that the module is allocated to a master.

Flashing green

Device is online with no connections in the
established state

Red

Critical link failure – failed communications module

Flashing red

Recoverable fault – an I/O connection has timed out

Module status

Off

No power applied to the device

Green

Device is online and has one or more I/O connections
in established state

Flashing green

Device needs commissioning due to missing,
incomplete, or incorrect configuration

Red

Critical fault – Device timed out or has an
unrecoverable fault

Flashing red

Recoverable fault – input or output short circuit

Auxiliary status

Off

No auxiliary power applied to the device

Green

Auxiliary power is applied to the device

I/O status

Off

I/O is not energized or is not valid

Yellow

I/O is energized and valid

DeviceNet 1732 ArmorBlock 16-Point I/O, Series A - 1732D-IB16M12M12,
1732D-IB16M12MINI, 1732D-16CFGM12M12, 1732D-16CFGM12MINI

Attribute

Value

Number of Inputs

16

Input type

61131-2 Type 3 compatible

Off-state input voltage, max

5V DC

Voltage, on-state input, max

30V DC

Voltage, on-state input, nom

24V DC

Voltage, on-state input, min

11V DC