General specifications – Rockwell Automation 1734-IB2_IB4_IB8, Series C POINT I/O Sink Input Module User Manual

Page 21

Advertising
background image

POINT I/O Input Modules 21

Publication 1734-IN051H-EN-E - April 2013

Indicators, module status

1 green/red, logic side

Indicators, input status

1734-IB2 – 2 yellow, logic side
1734-IB4 – 4 yellow, logic side
1734-IB8 – 8 yellow, logic side

POINTBus current, max

75 mA @ 5V DC

Power dissipation @ 28.8V DC, max

1734-IB2 – 0.7 W
1734-IB4 – 1.0 W
1734-IB8 – 1.6 W

Thermal dissipation @ 28.8V DC, max

1734-IB2 – 2.4 BTU/hr
1734-IB4 – 3.4 BTU/hr
1734-IB8 – 5.5 BTU/hr

Isolation voltage

50V (continuous), Reinforced Insulation Type
Tested @ 2500V DC for 60 s, field-side to system

Field power supply voltage, nom

24V DC

Field power voltage range

10...28.8V DC

Dimensions, HxWxD, approx.

56 x 12 x 75.5 mm

(2.2 x 0.47 x 2.97 in.)

Wiring category

(2)

1 – on signal ports

Wire size

Determined by installed terminal block.

Weight, approx.

1734-IB2 – 30.9 g (1.09 oz)
1734-IB4 – 31.8 g (1.12 oz)
1734-IB8 – 32.3 g (1.14 oz)

Enclosure type rating

None (open-style)

Keyswitch position

1

North American Temp Code

T4A

IEC Temp Code

T4

(1)

IEC 3 24V DC input compliant.

(2)

Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publication

1770-IN041.

General Specifications