Communicate with Your Module

I/O messages are sent to (consumed) and received from (produced) the
POINT I/O modules. These messages are mapped into the processor’s
memory. This POINT I/O address reserve module produces one byte of I/O
data. It does not consume I/O data.

1734-ARM Default Data Map

Wire the Address Reserve Module

The address reserve module requires no external wiring.

Use the Address Reserve Module

After creating the ControlLogix or CompactLogix systems I/O configuration
and user program, any I/O module in your system can be removed and
replaced by an address reserve module once the removed module is inhibited
using RSLogix 5000 programming software.

Inhibiting a module creates an I/O configuration and user program removing
all references to that module.

To use a 1734-ARM module in a MicroLogix system, configure a generic
module using RSLogix 500 programming software. Any user program
references to the slot position occupied by the 1734-ARM module must not
use another module’s parameters.

7

6

5

4

3

2

1

0

Produces (Rx)

0

0

0

0

0

0

0

0

Consumes
(scanner Tx)

No consumed data

Where: 0 = Off, 1 = On

ATTENTION

Use the RSLogix 5000 program software to inhibit the
1734-ARM module or the I/O module replaced by the
1734-ARM module. Failure to do so will result in the
controller continually trying to connect to a
noncommunicating module, thereby wasting connections.