10 SLC™ 500 4-Channel Analog I/O Modules

Publication 1746-IN008C-EN-P - May 2004

Switch Settings for the 1746-NIO4I, -NIO4V, -FIO4I, and -FIO4V

The NIO4I and NIO4V have 2 individual switches labeled 1 and 2. These switches
control the input mode of channel 0 and 1. A switch in the ON position configures
the channel for current input. A switch in the OFF position configures the channel
for voltage input.

External Power Switch for the 1746-NO4I and -NO4V

The NO4I and NO4V analog output modules have an external 24V dc power
switch, SW1, which gives you the option of using an external power supply. In the
UP position, power is drawn from an external power source. In the DOWN
position, power is drawn from the backplane of the module. The switch is located
on the analog module board. Switch orientation is also provided on the nameplate
of the module.

Choosing a Slot in the Chassis

Two factors determine where the analog module should be located in the chassis:
ambient temperature and electrical noise. Consider the following conditions when
selecting a slot for an analog module. Position the module:

in a slot away from an ac or high voltage dc modules

in the chassis closest to the bottom of the enclosure where the SLC 500
system is installed

away from the chassis power supply if installed in a modular system

Switch 1 = Channel 0

Switch 2 = Channel 1

1 2

N

O

Current

Voltage

External

Backplane

24V dc
Power
Selector

SW1

@JO$&/QQE

@JO$&/QQE

".

".