POINT I/O EtherNet/IP Adapter 17

Publication

1734-IN590B-EN-P - February 2005

Module Location

Starter module - left side of the 1734 system

Power Supply Specifications

Input Voltage Rating

24V dc nominal
10-28.8V dc range

Field Side Power
Requirements

24V dc (+20% = 28.8V dc maximum) @ 400mA maximum

Inrush Current

6A maximum for 10ms

Interruption

Output voltage will stay within specifications when input drops out
for 10ms at 10V with maximum load.

General Specifications

Indicators

4 red/green status indicators

Adapter status
PointBus status
Network activity status
Network status

2 green power supply status indicators:

System Power (PointBus 5V power)
Field Power (24V from field supply)

Power Consumption

4.5W maximum @ 28.8V dc

Power Dissipation

15.5W maximum @ 28.8V

PointBus Output
Current

1A maximum @ 5V dc ±5% (4.75 - 5.25)

Input Overvoltage
Protection

Reverse polarity protected

Thermal Dissipation

9.5 BTU/hr maximum @ 28.8V dc

Isolation Voltage

Tested to withstand 1800V dc for 60s

Field Power Bus

Nominal Voltage
Supply Voltage Range
Supply Current

24V dc
10-28.8V dc range
10A maximum

Dimensions Inches
(Millimeters)

3.0H x 2.16W x 5.25L
(76.2H x 54.9W x 133.4L)