Publication 1738-IN018A-EN-E - December 2004

ArmorPoint Extension Units, Series A 5

Extension Unit

Application Rules

All the following rules apply for both the 1738-EXT1 and 1738-EXT3
extension unit.

• For all adapters except the 1738-ADNX:

• Up to four extension units can be used per network adapter.

• For the 1738-ADNX adapter:

• Only one extension unit can be used if there are fewer than

32 modules on the backplane.

• The first module after an extension unit must be either a

1738-FPD or a 1738-EP24DC.

A 1738-EP24DC is needed:

if additional backplane power is needed because of

module current consumption, or

after 2 extension units.

A 1738-FPD is needed in all other configurations. The only

exception to this rule is if the modules in the segment after
the extension unit are only 1738-IT2IM12s, 1738-IR2M12s,
1738-OW4M12s, or 1738-OW4M12ACs. If only these modules
are used, no 1738-FPD or 1738-EP24DC is needed.

• The number or mix of modules you use between extension

cables does not matter as long as you do not exceed the rated
adapter or 1738-EP24DC current output.