Publication 1738-IN020A-EN-E - June 2004

ArmorPoint I/O 24V dc Expansion Power Supply, Series A 7

Specifications

Following are specifications for the 1738-EP24DC power supply.

1738-EP24DC Power Supply
I/O Module Capacity

5 to 17 I/O modules depending on each module’s current rating.

Power Supply

In order to comply with CE Low Voltage Directives (LVD), you must use a Safety
Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to
power the adapter.

Inputs Voltage Rating

12V dc, 24V dc nominal

10-28.8V dc range

Operating Voltage

10-28.8V dc

Input Current, Maximum

6A for 10ms

Backplane Output Current

5V dc, 1.3A

Field Side Power Requirements, Maximum

24V dc (+20% = 28.8V dc) @ 400mA

Indicators

1 Green Field Power Status Indicator

1 Green 5V System Power Indicator

Module Location

Between I/O modules in 1738 system

Breaks field power bus

PointBus Output Current

1 A at 10-19.2V input; 1.3 A at 19.2-28.8V input

Input Overvoltage Protection

Reverse polarity protected

Interruption

Output voltage will stay within specifications when input drops out for 10ms at
10V with maximum load

General Specifications

Power Consumption, Maximum

9.8W @ 28.8V dc

Power Dissipation, Maximum

3.0W @ 28.8V dc

Thermal Dissipation, Maximum

10.0 BTU/hr @ 28.8V dc

Isolation Voltage

(continuous-voltage withstand rating)

50V rms

Tested at 1250V ac rms for 60s

Field Power Bus

Supply Voltage

Voltage Range

Supply Current


12V dc, 24V dc nominal

10-28.8V dc range

10 A maximum

Dimensions Inches (Millimeters)

1.25H x 2.63W x 4.25D (31.75H x 66.80W x 107.95D)

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20 to 60°C (-4 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):

5-95% non-condensing

Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):

Operating 30g

Non-operating 50g

Vibration

IEC60068-2-6 (Test Fc, Operating):

5g @ 10-500Hz

ESD Immunity

IEC 61000-4-2:

6kV contact discharges

8kV air discharges

Advertising