Install the module – Rockwell Automation 1734-FPD, Series B POINT I/O Field Potential Distributor Modules Installation Instructions User Manual

Page 7

Advertising
background image

POINT I/O Field Potential Distributor Modules 7

Publication 1734-IN059D-EN-E - April 2013

Install the Module

To install the module on the DIN rail, proceed as follows:

1. Position the module vertically above the DIN rail.

2. Engage the interlocking pieces with the unit on the left.

3. Press down firmly to install the module on the DIN rail. The locking mechanism

locks the module to the DIN rail.

ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The
use of other DIN rail materials (for example, aluminum or plastic) that can
corrode, oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately.

WARNING: When you insert or remove the module while backplane power is
on, an electrical arc can occur. This could cause an explosion in hazardous
location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance that can affect module operation.

Advertising