Environmental specifications, General specifications – Rockwell Automation 1738-AENT, Series B ArmorPOINT I/O EtherNet/IP Adapter User Manual

Page 15

Advertising
background image

1738 ArmorPOINT I/O EtherNet/IP Adapter 15

Publication 1738-IN031A-EN-P - July 2013

Thermal dissipation, max

9.5 BTU/hr @ 28.8V DC

Isolation voltage

Type Tested @ 500V AC for 60 s:
• Comm to system
• Comm to user power
• User power to system
• User power to ground
• System to ground

Field power supply

10...28.8V DC @ 10A

Field power output

10...28.8V DC @ 9A

Module input

10...28V DC @ 1000 mA

POINTBus output, max

5V DC @ 1.0A

Dimensions (HxWxD), approx.

112.0 x 72.0 x 65.0 mm (4.41 x 2.83 x 2.56 in.)

Mounting type

Metal panel

Enclosure type rating

Meets IP65/66/67/69K (when marked)

Terminating base screw torque

0.8 Nm (7 lb-in)

Wiring category

(1)

1 – on power ports

1 – on communications ports

Weight, approx.

0.36 Kg (0.8 lb)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-IN041

.

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...60 °C (-4...140 °F)

Temperature, ambient air, max

60 °C (140 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% noncondensing

General Specifications

Attribute

Value

Advertising