Wiring digital modules – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 30

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

14 Install POINT I/O Modules

Wiring Digital Modules

Refer to this section to wire digital modules.

1734-IB2, 1734-IB4, and 1734-IB8 Sink Input Modules

1734-IB2 Module Wiring Diagram

24VDC

Sink

Input

Module

Status

Network

Status

1734

IB2

NODE:

0

1

24VDC

Sink

Input

Module

Status

Network

Status

1734

IB4

NODE:

0

1

2

3

24VDC

Sink

Input

Module

Status

Network

Status

1734

IB8

NODE:

0

1

2

3

4

5

6

7

Status of Input 0

Status of Input 1

Input 0

NC

C

V

Input 1

NC

C

V

Input = 0 and 1
NC = No Connection (2 and 3)
C = Common (4 and 5)
V = Supply (6 and 7)

Input 0

C

V

Input 1

C

V

Input 2

Input 3

Status of Input 2

Status of Input 3

Input = 0, 1, 2 and 3
C = Common (4 and 5)
V = Supply (6 and 7)

1734-IB2

1734-IB4

1734-IB8

Input 0

Input 1

Input 2

Input 3

Input 4

Input 5

Input 6

Input 7

Input = 0, 1, 2, 3, 4, 5, 6 and 7
V and C are daisychained from either the adapter,
1734-FPD module, 1734-EP24DC power supply, or a
user-supplied auxiliary terminal block.

Status of Input 0

Status of Input 1

Status - Input 0 & 4

Status - Input 1 & 5
Status - Input 2 & 6

Status - Input 3 & 7

Channel

Input

Common

Voltage

0

0

4

6

1

1

5

7

Connect common on 3-wire proximity switches. 12/24V DC is supplied
through the internal power bus.

Prox

In 0

In 1

NC

C

V

V

C

NC

Prox

V = 12/24V DC
C = Common

3-wire

Sink Input

2-wire

3

5

7

0

1

2

4

6

Advertising