Environment and enclosure – Rockwell Automation 1734-TOP_TOPS_TOP3_TOP3S Point I/O Terminal Base Installation Instructions User Manual

Page 3

Advertising
background image

POINT I/O One-piece Terminal Bases 3

Publication 1734-IN028B-EN-P - April 2010

Environment and Enclosure

IMPORTANT

Identifies information about practices or circumstances that can
lead to personal injury or death, property damage, or economic
loss. Attentions help you to identify a hazard, avoid a hazard and
recognize the consequences.

SHOCK HAZARD

Labels may be located on or inside the equipment, for example, a
drive or motor, to alert people that dangerous voltage may be
present.

BURN HAZARD

Labels may be located on or inside the equipment, for example, a
drive or motor, to alert people that surfaces may be dangerous
temperatures.

ATTENTION

This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as
defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft)
without derating.

This equipment is considered Group 1, Class A industrial
equipment according to IEC/CISPR 11. Without appropriate
precautions, there may be difficulties with electromagnetic
compatibility in residential and other environments due to
conducted and radiated disturbances.


This equipment is supplied as open-type equipment. It must be
mounted within an enclosure that is suitably designed for those
specific environmental conditions that will be present and
appropriately designed to prevent personal injury resulting from
accessibility to live parts. The enclosure must have suitable
flame-retardant properties to prevent or minimize the spread of
flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or
equivalent) if non-metallic. The interior of the enclosure must be
accessible only by the use of a tool. Subsequent sections of this
publication may contain additional information regarding specific
enclosure type ratings that are required to comply with certain
product safety certifications.


In addition to this publication, see:

Industrial Automation Wiring and Grounding Guidelines,
Rockwell Automation publication

1770-4.1

, for additional

installation requirements.

NEMA Standard 250 and IEC 60529, as applicable, for
explanations of the degrees of protection provided by
different types of enclosure.

Advertising