Module specifications, Electrical specifications physical specifications – Rockwell Automation 1746-NT8 SLC 500 Thermocouple/mV Analog Input Module/ Instructions User Manual

Page 17

Advertising
background image

SLC 500 Thermocouple/mV Analog Input Module 17

Publication 1746-IN015C-EN-P - July 2001

Module Specifications

Electrical Specifications

Physical Specifications

Backplane Current Consumption

120 mA at 5V dc, 70 mA at 24V dc

Backplane Power Consumption

2.28W maximum (0.5W at 5V dc, 1.68W at 24V dc)

Number of Channels

8 (backplane and channel-to-channel isolated)

I/O Chassis Location

Any I/O module slot except 0

A/D Conversion Method

Sigma-Delta Modulation

Input Filtering

Low pass digital filter with programmable notch (filter)
frequencies

Normal Mode Rejection
(between [+] input and [-] input)

Greater than 100 dB at 50/60 Hz

Common Mode Rejection
(between input and ground)

Greater than 100 dB at 50/60 Hz

Input Filter Cut-Off Frequencies
2.6 Hz at 10 Hz filter frequency
13.1 Hz at 50 Hz filter frequency
15.72 Hz at 60 Hz filter frequency
65.5 Hz at 250 Hz filter frequency

Greater than 100 dB at 50/60 Hz

Calibration

Module autocalibrates at power-up and approximately
every two minutes thereafter

Input Over voltage Protection

±30V dc continuous, 600W pulsed for 1 msec.

Isolation

500V dc for 1 minute between inputs and chassis
ground, and between inputs and backplane.
12.5V dc continuous between channels.

LED Indicators

9 green status indicators, one for each of 8 channels
and one for module status

Module ID Code

3533

Maximum Wire Size

One 14 AWG wire or two 22 AWG wires per terminal

Replacement Terminal Block

1746-RT34

Advertising