12 ArmorPoint I/O Synchronous Serial Interface (SSI) Absolute Encoder Module, Series A

General Specifications

LED Indicators

1 green run status, logic side

1 green up status, logic side

1 green down status, logic side

1 green comp status, logic side

1 green/red network status, logic side

1 green/red module status, logic side

PointBus Current, Maximum

110mA

Power Dissipation, Maximum

0.94 W @ rated load

Thermal Dissipation, Maximum

3.21 BTU/hr. @ rated load

Isolation Voltage

(continuous-voltage withstand rating)

50V rms

Tested at 1250V ac rms for 60s

Dimensions Inches (Millimeters)

1.25H x 2.63W x 4.25D (31.75H x 66.80W x 107.95D)

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20 to 60°C (-4 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):

5-95% non-condensing

Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):

Operating 30g

Non-operating 50g

Vibration

IEC60068-2-6 (Test Fc, Operating):

5g @ 10-500Hz

ESD Immunity

IEC 61000-4-2:

6kV contact discharges

8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz

EFT/B Immunity

IEC 61000-4-4:

±2kV at 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:

±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

±2kV line-earth(CM) on shielded ports

Conducted RF Immunity

IEC 61000-4-6:

10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Emissions

CSPR 11:

Group 1, Class A

Enclosure Type Rating

Meets IP65/66/67 (when marked)

Mounting Base Screw Torque

#8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel

Weight

Imperial (Metric)

0.637 lb. (0.289 kg)

Wiring Category

3

2 - on signal ports

Advertising