Default data map – Rockwell Automation 1734-VHSC24 Point I/O Very High Speed Counter Module User Manual

Page 14

Advertising
background image

14 POINT I/O 5V DC and 24V DC Very High Speed Counter Module

Publication 1734-IN003F-EN-E - January 2014

When you send a configuration to the module, you check it for consistency before
applying it.

Monitor this PE bit with your user program to isolate any problems with an improperly
configured module. If the configuration is acceptable, the counter ASIC is disabled while
the ASIC is loaded with new operational parameters. Outputs can turn off during this
reconfiguration.

Default Data Map

Message size: 6 or 10 Bytes

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Produces
(scanner Rx)

Channel 0 value of present counter state (LSW)

Channel 0 value of present counter state (MSW)

PE

EF

NR

0

FS

FS

OS

OS

0

ZS

BS

AS

C1

C0

ZD

0

Where:

LSW = Least significant word

MSW = Most significant word

PE = Programming error

EF = EEPROM fault status

NR = Not ready status bit

FS = Output fault status bit – bit 10 for output 0, bit 11 for output 1

OS = Output on/off status bit – bit 8 for output 0, bit 9 for output 1

ZS = Z input status

BS = B input status

AS = A input status

C = Stored data count

ZD = Zero frequency detected

Message size: 2 or 4 Bytes

08...15

07

06

05

04

03

02

01

00

Consumes
(scanner Tx)

0

0

0

0

0

0

VR

CP

CR

0

DS

ES

0E

F0

DS

ES

0E

F0

Where:

VR = Value reset of stored/accumulated count

CP = Counter preset

CR = Counter reset

DS = Diagnostic speed

ES = Electronic fuse select

OE = Output enable

FO = Force output