Connect the i/o cord sets to the module, Network connector, M12-style input connectors i/o connector – Rockwell Automation 1732D-8I8O1212D DNet ArmorBlock Network Powered 8-input/8-output Module IN User Manual

Page 9: M12-style 5-pin female input connector

Advertising
background image

DeviceNet ArmorBlock Network Powered 8-input/8-output Module 9

Publication

1732D-IN010A-EN-E - April 2009

Connect the I/O Cord Sets to the Module

The ArmorBlock DeviceNet family has 5-pin micro-style connectors.
We provide caps to cover the unused connectors on your module.

Connect the quick-disconnect cord sets that you selected for your module to
the appropriate ports.

Network Connector

Refer to the pinout diagram for the network connector.

M12-style Input Connectors

I/O Connector

Refer to the pinout diagram for the I/O connector.

M12-style 5-pin Female Input Connector

Male

Female

(View into Connector)

Pin 1

Drain

Pin 2

V+ (Red)

Pin 3

V- (Black)

Pin 4

CAN_H (White)

Pin 5

CAN_L (Blue)

41452

44175

(View into Connector)

Pin 1

Sensor Source Voltage

Pin 2

Output

Pin 3

Return

Pin 4

Input

Pin 5

PE

41452

Advertising