Backlight Replacement 9

Publication 2711P-IN019D-EN-P - February 2007

8. Insert the new backlights and then secure each with the same screws from

step 7 and torque to 0.117 Nm (1.04 lb-in).

9. Attach the LCD display connector to the circuit board (shown in step 3 on

page 6).

10. Attach the backlight connector to the circuit board (shown in step 4 on

page 7).

11. Secure the LCD display.

a. Attach the display bracket then secure the display in the bracket for the

700 series C display.

b. Attach the four screws for all other displays.

Use the following chart to tighten the screws.

12. Replace display module bezel.

See Replace Display Module Bezel.

Backlight Disposal

Screw Size

Torque

#4

0.68 Nm (6 lb-in)

IMPORTANT

The backlight in this product contains mercury. Dispose of the backlight per
applicable laws.