PanelView Plus and VersaView CE Logic Module Pullup Board 3

Publication 2711P-IN028A-EN-P - December 2005

About the Pullup Board

The PanelView Plus/VersaView CE Logic Module Pullup Board corrects intermittent
terminal resets (reboot or power cycle) that have typical reset cycle rates of
approximately 60 seconds. In addition, a 50 second lock-up is typically observed
during ‘Invoking Test Monitor’ terminal boot screen.

Affected product Series/Revisions and Date Codes are:

Install the Pullup Board

Product

Catalog Numbers

Series and Revisions

Data Code

PanelView
Plus/VersaView CE
Terminals

2711P-x7, 2711P-x10,
2711-x12, 2711P-x15,
6182H-x7, 6182H-x10,
6182H-x12, 6182H-x15

Series A, Revisions A to D

0203 thru 0705
(Manufacturing dates
February 2003 to
July 2005)

PanelView
Plus/VersaView CE Logic
Modules

2711P-RP, 2711P-RP1,
2711P-RP2, 6189-RP,
6189-RPRH, 6189-RPEH

Series A, Revision A through
Series C, Revision A

0203 thru 0705
(Manufacturing dates
February 2003 to
July 2005)

WARNING

If you connect or disconnect any communication cable with
power applied to this module or any device on the network, an
electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or
the area is nonhazardous before proceeding.

Logic Module Series and
Revision

Terminal Series and
Revision

Date Codes