Publication 2361-5.29 April 1999

Bridge Fan and Capacitor Replacement (for 3000A 1395 DC Drives)

3

Preliminary Steps

Before replacing the bridge fan and fan capacitor, shut off the drive power.
Wait five minutes for all voltage to discharge. Open the bridge bay door
and remove all Lexan™ guards that shield the bridge fan.

Note: The bridge fan and fan capacitor must be replaced together.

Removing the Bridge Fan

1. Using a meter, test the voltage across the three phases of the AC line.

2. Remove the air filter from the fan inlet cover.

3. Remove the bolts which secure the support beam and take the beam out

(see Figure 1).

4. Remove the fan inlet cover screws (as shown in Figure 1). Remove the

cover from the assembly.

5. Disconnect the power connector for the fan.

6. Remove the four screws from the fan mounting bracket (as shown in

Figure 1).

7. Remove the four screws which attach the fan to the bracket.

Figure 1
Replacing the Bridge Fan

!

ATTENTION: If there is any voltage present, remove the
source of the voltage. Check for voltages again before
proceeding to the next step.

Fan Inlet Cover
Screws

Support Beam

Power Connector

Bracket Mounting

Screws