Rockwell Automation AADvance Controller PFH avg and PFD avg Data User Manual

Page 16

Advertising
background image

1-10

Document: 553847

(ICSTT-RM449_EN_P) Issue 04:

PFH avg and PFD avg Data (AADvance Controller)


Example 3

Example 3

Example 3

Example 3

SIL3 SIF with 2 inputs on dual input modules and 1 output with a manual test interval
of 1 year and MTTR = 8 hours as 1oo2 de-energize to trip.

Refer to Table 3

Example 4

Example 4

Example 4

Example 4

This illustrates a SIL 3 with 1 dual input and 2 outputs, with a manual test interval of 1
year and MTTR = 8 hours, configured as 1oo2 de-energize to trip.

Refer to Table 3