ICM-IN001A-EN-P - March 2009

Non-Operating Temperature
IEC 60068-2-1 (Test Ab, Unpackaged
Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged
Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged
Non-operating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp
Heat):

5…95% non-condensing

Vibration
IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):

15 g

Nonoperating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):

20 g

Emissions
CISPR 11:

Group 1, Class A

ESD Immunity
IEC 61000-4-2:

4 kV contact discharges
8 kV air discharges

Radiated RF Immunity
IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM
from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM
at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM
at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz

EFT/B Immunity
IEC 61000-4-4:

±4 kV at 5 kHz on power ports
±2 kV at 5 kHz on communications ports