Measure Line-To-Line Voltages

Verify that the drive input voltage has an unbalance that is less that 3%.

Ground The Drive

Ensure that drive grounding is properly connected as illustrated below. The
ground wire return between the motor and the drive must be terminated directly
to the drive PE terminal. Shielded cable is recommended but not always needed.
Refer to the product-specific documentation for requirements.

Protect The Drive

Ensure that the proper sized input fuses or circuit breakers are installed prior to
applying power to the drive.

Verify Your Installation

Ensure that all input and output power wiring is correctly wired and securely
fastened prior to applying power to the drive.

Unbalanced Percent = (Vmax - Vmin) x 100

(Vavg)

Vavg = (VAB + VBC + VCA)

3

Where:

Vmax = maximum line-to-line RMS voltage

Vmin = minimum line-to-line RMS voltage

Where:

VAB, VBC, VCA = line-to-line voltage

(OPTIONAL ENCLOSURE)

AC DRIVE

PE PE

R

U

S

V

T

W

BUILDING GROUND POTENTIAL

CONDUIT

MOTOR FRAME

MOTOR

Connection to Drive Structure
or Optional Cabinet
Via Conduit Connector

Panel Ground Bus

Ground Bus Connected
Directly to Drive PE Terminal

Motor

Frame

Ground