Mass flow computation, Sds-8019 trusted, Industrial control system trusted – Rockwell Automation T8019 Trusted Process Control Algorithms User Manual

Page 2: Process control algorithms-t8019

Advertising
background image

SDS-8019
Trusted

TM

Industrial Control System

Trusted

TM

Process Control Algorithms-T8019

ICS Triplex

Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-

www.icstriplex.com

MASS FLOW COMPUTATION

MASS
FLOW

OUT

=P

P
T
C
Z

m

e
h

The mass-flow computation block provides the mass
flow corrected for the current operating conditions.

(

)

(

)

(

)

+

+

Ч

Ч

Ч

Ч

Ч

Ч

=

273

T

14.7

P

h

e

m

Z

C

OUT

=P is the differential pressure, P is pressure and T is
temperature. C, Z, m, e and h are intended to be
constant values. All parameters are of type REAL.
=P and P are in psi, T is in

0

C.

If T=-273, a divide by zero error condition is generated,
this is to increment the associated error counter and
the mass flow function is to return a value of -1. Over
and underflow conditions are to result in an output
value of -1 and increment the associated error counter.

DEVIATION ALARM

DEV_AL

PV

SP

DEV

US

DEV

DS

DEV

HI

DEV

LO

The deviation alarm function block takes the current
process variable (PV) and set-point (SP), together with
the up-scale and down-scale deviation between the PV
and SP (DEV

US

and DEV

DS

respectively). PV, SP,

DEV

US

and DEV

DS

are of type REAL, both outputs

(DEV

HI

and DEV

LO

) are of type Boolean.

DEV

HI

= ( (PV – SP) DEV

US

)

DEV

LO

= ( (SP – PV) DEV

DS

)

If an overflow condition occurs during the execution of
the function, DEV

HI

is to be set to PV>0, DEV

LO

to

PV<0 and the “overflow” error counter is to be
incremented.
PV, SP, DEV

US

and DEV

DS

must be finite, i.e. not

±infinities or NaNs.