Communications Modules (T3150A)


6

Industrial Control Services

Application

Communications Port Connections

Each communications port has a DB-25, female connector on
the front of the module. The RS232 and RS422/485 signals
are internally connected to the DB-25 connector pins as shown
in Table 1. Refer to Figures 3 through 5 for recommended
communications cable requirements and connections.

Table 1. Communications Port Pin-out.

Pin No.

RS232

Signal

RS422/485

Signal

2

TX

(not used)

3

RX

(not used)

7

GND

GND

9

(not used)

+ 5 VDC

10

(not used)

TX (-)

11

(not used)

RX (-)

22

(not used)

TX (+)

23

(not used)

RX (+)

Recommended Cable Type

For multidrop and Guarded Peer-Link communications a
Belden cable type 813x (where x = number of pairs) is
recommended. The cable has the following characteristics
that are important:

120 Ohm, Characteristic Impedance

Twisted Pairs

Overall shield

Communications Configurations

The communications module supports a variety of
communications configurations which are shown in Figures 3
through 5. Figure 3 illustrates two point-to-point