Rockwell Automation Publication GMSI10-UM019C-EN-P - June 2011

12 Installing the XM-441 Expansion Relay Module

XM Installation
Requirements

This section describes wire, power and grounding requirements for an XM
system.

Wiring Requirements

Use solid or stranded wire. All wiring should meet the following requirements:

• 14 to 22 AWG copper conductors without pretreatment; 8 AWG

required for grounding the DIN rail for electromagnetic interference
(emi) purposes

• Recommended strip length 8 millimeters (0.31 inches)

• Minimum insulation rating of 300V

• Soldering the conductor is forbidden

• Wire ferrules can be used with stranded conductors; copper ferrules

recommended

Power Requirements

Before installing your module, calculate the power requirements of all modules
interconnected via their side connectors. The total current draw through the
side connector cannot exceed 3A. Refer to the specifications for the specific
modules for power requirements.

ATTENTION

See the XM Documentation and Configuration Utility CD
for Hazardous Locations installation drawings. The XM
Documentation and Configuration Utility CD is packaged
with the XM modules.

ATTENTION

A separate power connection is necessary if the total
current draw of the interconnecting modules is greater than
3A.