XM-946 EODS Relay Terminal Base 15

Publication

GMSI10-IN017A-EN-P - May 2010

Terminal Assignments

WARNING

EXPLOSION HAZARD
Do not disconnect equipment unless power has been removed
or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power
has been removed or the area is known to be nonhazardous.
Secure any external connections that mate to this equipment by
using screws, sliding latches, threaded connectors, or other
means provided with this product.

ATTENTION

The terminal block assignments are different for different
terminal base units. The following table applies only to the
XM-946. Refer to the installation instructions for the specific
terminal base unit for its terminal assignments.

IMPORTANT

The primary 24V dc needs to be wired to terminal 0 to
provide power to XM-946 and other XM modules located on
the DIN rail. Terminal 3 should be used if a second, or
redundant, power supply is needed. Note that terminal 3
provides redundant power only to the XM-946. It does not
serve other terminal base units.

No.

Description

No.

Description

0

24V in 1

26

No connection

1

24V common

27

Shutdown relay 3 common contact 1

2

Reset relay

28

Alarm relay common contact 2

3

24V in 2

29

Alarm relay common contact 1

4

Shutdown relay 1 N.O. contact 2

30

No connection

5

Shutdown relay 1 N.O. contact 1

31

Chassis ground

6

Shutdown relay 2 N.O. contact 2

32

No connection

7

No connection

33

No connection