(T3454) AC Isolated Digital Output Module


P D - 6 0 1 8 M a r - 0 6

13

Specifications

Safetybus Power

0.75 load units

Number of Outputs

8 circuits, individually
isolated

Voltage Range

90 to 130 VAC

Frequency Range

47 to 63 Hz

Load Current

2 amps maximum per output
0

°

to 60

°

C

16 amps maximum per
module 0

°

to 40

°

C, derated

linearly to 12 amps at 60

°

C

Minimum Load

50 mA

On State Drop

2.0 volts maximum

Surge Current

15 amps, 20 msec

Output Leakage

2.5 mA maximum

Fusing

One 3 A, 250 V, fast-acting
(3AG) per output, located
inside module

Turn-On Delay

½ AC cycle, maximum

Turn-Off Delay

½ AC cycle, maximum

Heat Dissipation

32 Watts, 107 BTUs/hour

Over Voltage Protection

275 VAC, continuous

Isolation

2500 volts minimum (field
wiring to control logic)
2500 volts minimum
(channel to channel)

Operating Temperature

0

°

to 60

°

C

(32

°

to 140

°

F)

Storage Temperature

-40

°

to 85

°

C

(-40

°

to 185

°

F)