SDS-8292
Trusted

TM

Industrial Control System

Trusted

TM

Power Distribution Unit MCB 24V-T8292

ICS Triplex

Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-

www.icstriplex.com

BLOCK DIAGRAM

ELECTRICAL SPECIFICATION

Voltage Range

22-28V dc

Supply Current

60A maximum

Input Supply Indication

2-off green LEDs – one per feeder

MCB Operation Indication

10-off red LEDs – one per MCB

MCB Outputs

8-off 24V dc @ 20A
2-off 24V dc @ 3A

Leakage Current (open MCB)

0.6mA @ 28V dc maximum

Common Alarm Output

1-off N/O contact

Maximum Switching Voltage

60V dc or 125V ac

Maximum Switching Current

0.5A

Minimum Load

5V dc @ 1mA

MECHANICAL
SPECIFICATION


Dimensions (HxWxD):
108mm x 240mm x 109mm
(4.2ins x 9.4ins x 4.3ins)

Weight:
823g
(1.8lbs)

ENVIRONMENTAL


Operating Temperature:

Forced Cooled
-5

°C to 60°C

(23

°F to 140°F)


Operating Humidity:
5 to 95%, non-condensing

Vibration:
10 to 57Hz

±0.075mm

57 to 500Hz 1.0g

Shock:
15g, ½ sine wave, 11ms

EMI (IEC 801):
ESD
Air discharge to 15kV
Contact discharge to 8kV

Radiated Fields
10V/m, 27MHz to
500MHz

Transients and Bursts
2kV, 2.5kHz for
t=60 seconds