I/o smartslot cable type tc-506, Figure 6 i/o smartslot cable type tc-506, Trusted – Rockwell Automation TC500 Trusted I/O SmartSlot Cables User Manual

Page 14: I/o smartslot cables version 2 tc-500

Advertising
background image

Trusted

TM

I/O SmartSlot Cables Version 2 TC-500

Issue 13 Apr 10

PD-TC500

14

6. I/O SmartSlot Cable Type TC-506

This type of cable, and the modules it is used with, is shown in Figure 6 below.

Figure 6 I/O SmartSlot Cable Type TC-506

This type of Trusted

TM

I/O SmartSlot Cable is designed for use with digital 24V/120V dc or analogue

output modules and is suitable for connecting output signals from the module to internal terminals.

Two multi-core cables are required for this application. The chassis end of the multi-core 1 is fitted
with a 96-way type ‘C’ connector housed in a single-width hood (TC-500). The other end of multi-core
1 is left as a ‘flying lead’ enabling the cable to be terminated as required, e.g. connected to conditioned
field terminals. The non-chassis end of multi-core 2 is fitted with a 6-way Amp plug used to connect
power to the field from a T8290 or T8297 and is made up of five individual 2.5mm wires contained
within Rilgain sleeving.

The flying leads are sleeved with identity ferrules marked CH1, CH2, CH3 etc. for channel terminations
or V FIELD RTNGRP1 to V FIELD RTNGRP5 for group reference terminations.

The 0V connections at the flying leads end allows a module reference so that it can measure its output
voltage, these must be connected to the field 0 Volts.

The flying lead multi-core contains isolated power group field 0 Volts which connect to field 0V supply.
Commoning of the reference is obtained by a connection to this field supply.

Multi-core 1 is stripped back 1.5m at both ends. Multi-cores 1 and 2 are shrouded in nylon Rilgain
sheathing. The ends of the sheathing are heated, or over sleeved as required to prevent fraying.

At the chassis end, a sheathed braid allows the connector hood to be wired to safety earth. At the
remote end, the multicore screen drain is wired to a green wire to allow connection to screen earth.

Module

T8444

T8448

T8449

T8451

T8461

T8471

T8480