Specifications, Trusted, Analogue input fta t8831 – Rockwell Automation T8831 Trusted 40 Channel Analogue FTA Non-incendive User Manual
Page 12
Trusted
TM
Analogue Input FTA T8831
Issue 6 Sep 05
PD-T8831
12
5. Specifications
Voltage Range
18 to 32V dc
Maximum Normal Output Current I
sc
(Field
Supply)
81mA
Maximum Normal Output Voltage V
oc
(Field
Supply)
32V as voltage range above
Maximum External Capacitance C
a
5µF for methane, 0.3µF for groups A and B,
in accordance with AANSI/ISA 12.12.01-
2000
Maximum External Inductance L
a
10mH for methane or group B, in
accordance with AANSI/ISA 12.12.01-2000
Operating Temperature
-5
0
C to 60
0
C (23
0
F to 140
0
F)
Non-operating Temperature
-25
0
C to 70
0
C (-13
0
F to 158
0
F)
Operating Humidity
5 to 95% RH non-condensing.
Environmental Specifications
Refer to Document 552517
Dimensions
Height
Width
Depth
111mm (4.4ins)
335mm (13.2ins)
51mm (2ins)
Weight
900gms (2lbs)