Thermostat Contact Rating: 125 VAC, 15 A, Opens at 227 °C (440 °F) Closes at 182 °C (359 °F)

Application Cross-Reference

Note 1:

Always check resistor ohms against minimum resistance for drive being used.

Note 2:

Duty cycle listed is based on full speed to zero speed deceleration.
For constant regen at full speed, duty cycle capability is half of what is listed.
Application Type 1 represents maximum capability up to 100% braking torque where possible.
Application Type 2 represents more than 100% braking torque where possible, up to a maximum of 150%.

Drive and Motor
Size
kW (HP)

Part Number

Resistance
Ohms ±5%

Continuous Power
kW

Max Energy
kJ

Max Braking
Torque
% of Motor

Application Type 1

Application Type 2

Braking Torque
% of Motor

Duty Cycle
%

Braking Torque
% of Motor

Duty Cycle
%

100…120 Volt AC Input Drives

0.75 (1)

AK-R2-091P500

91

0.086

17

218%

100%

23%

150%

31%

1.1 (1.5)

AK-R2-091P500

91

0.086

17

164%

100%

16%

148%

11%

200…240 Volt AC Input Drives

0.37 (0.5)

AK-R2-091P500

91

0.086

17

293%

100%

46%

150%

31%

0.75 (1)

AK-R2-091P500

91

0.086

17

218%

100%

23%

150%

15%

1.5 (2)

AK-R2-091P500

91

0.086

17

109%

100%

11%

109%

11%

2.2 (3)

AK-R2-047P500

47

0.166

33

144%

100%

15%

144%

11%

4 (5)

AK-R2-047P500

47

0.166

33

79%

79%

11%

N/A

N/A

5.5 (7.5)

AK-R2-030P1K2

30

0.26

52

90%

90%

10%

N/A

N/A

7.5 (10)

AK-R2-030P1K2

30

0.26

52

66%

66%

10%

N/A

N/A

11 (15)

See Note 3

15

0.52

104

90%

90%

10%

N/A

N/A

15 (20)

See Note 3

15

0.52

104

66%

66%

10%

N/A

N/A

400…480 Volt AC Input Drives

0.37 (0.5)

AK-R2-360P500

360

0.086

17

305%

100%

47%

150%

31%

0.75 (1)

AK-R2-360P500

360

0.086

17

220%

100%

23%

150%

15%

1.5 (2)

AK-R2-360P500

360

0.086

17

110%

100%

12%

110%

11%

2.2 (3)

AK-R2-120P1K2

120

0.26

52

197%

100%

24%

150%

16%

4 (5)

AK-R2-120P1K2

120

0.26

52

124%

100%

13%

124%

10%

5.5 (7.5)

AK-R2-120P1K2

120

0.26

52

90%

90%

10%

N/A

N/A

7.5 (10)

AK-R2-120P1K2

120

0.26

52

66%

66%

10%

N/A

N/A

11 (15)

See Note 3

60

0.52

104

90%

90%

10%

N/A

N/A

15 (20)

See Note 3

60

0.52

104

66%

66%

10%

N/A

N/A

600 Volt AC Input Drives

0.37 (0.5)

AK-R2-360P500

360

0.086

17

274%

100%

46%

150%

31%

0.75 (1)

AK-R2-360P500

360

0.086

17

251%

100%

23%

150%

15%

1.5 (2)

AK-R2-360P500

360

0.086

17

172%

100%

11%

150%

8%

2.2 (3)

AK-R2-120P1K2

120

0.26

52

193%

100%

24%

150%

16%

4 (5)

AK-R2-120P1K2

120

0.26

52

185%

100%

13%

150%

9%

5.5 (7.5)

AK-R2-120P1K2

120

0.26

52

141%

100%

9%

141%

7%

7.5 (10)

AK-R2-120P1K2

120

0.26

52

103%

100%

7%

103%

7%

11 (15)

See Note 3

60

0.52

104

141%

100%

9%

141%

7%

15 (20)

See Note 3

60

0.52

104

103%

100%

7%

103%

7%

AC Drive

4

BR1

BR+

BR2

BR-

!

ATTENTION: AC drives do not offer protection for externally mounted brake resistors,
especially in the case of brake IGBT failure. A risk of fire exists if external braking
resistors are not protected. External resistor packages must be protected from over
temperature or the protective circuit shown, or equivalent, must be supplied.

AC Drive

5

Thermostat

Connectors

Power On

R (L1)
S (L2)
T (L3)

Power Source

DB Resistor Thermostat

Power Off

M

M

(Input Contactor) M

Three-Phase

AC Input

!

ATTENTION:
Resistor temperature may exceed 200
degrees C.

Note 3:

For 11 and 15 kW (15 and 20 HP) normal duty external resistor applications, use two
7.5 kW (10 HP) size resistors wired in parallel.