Safety considerations, Specifications – Rockwell Automation T3122 ICS Regent Processor Modules User Manual

Page 18

Advertising
background image

Processor Modules (T3110, 11, 12, 20, 21, and 22)


1 8

Industrial Control Services

Safety Considerations

Processor module catalog numbers T3110, T3112, T3120 and
T3122 are TÜV certified for Risk Class 5 safety critical

applications. Catalog numbers T3111 and T3121 (220 VAC
powered modules) have not been certified as they do not meet
the DIN VDE 0110 requirements for creepage and clearances.

Specifications

Voltage Range

T3110/T3120:
T3111/T3121:
T3112/T3122:


85 to 132 VAC
170 to 263 VAC
20 to 30 VDC

Frequency Range

T3110/T3120:
T3111/T3121:
T3112/T3122:


47 to 63 Hz
47 to 63 Hz

Maximum Load

100 VA

Fusing

2 A, 250 V, slo blo (3AG),

(located on controller chassis)

Use with Chassis

T3110/T3120:
T3111/T3121:
T3112/T3122:


T3100
T3101
T3102

Power Hold-Up Time

10 msec, minimum

Heat Dissipation

46 Watts, 156 BTUs/hour

Fault Contact Rating

(Class II Connection Only)

Load Current (max.):

Load (min.):

Voltage (max.):

Switching Capacity

(max.):



1 amp
10 mV, 0.1 mA
30 VAC, 42.5 VDC

30 VA, 42.5 VAC (resistive)

Advertising