Temp” button functions, Man. def” (manual defrost) button function, Loss of power – Bally Refrigerated Boxes SmartVap Electronically Controlled System User Manual

Page 2: Restore original factory default settings

Advertising
background image

“Temp” Button Functions

To view TEMP settings (in sequence listed below), push and release the “Temp” button.

To adjust settings, hold down the “Temp” button while pushing “Up” or “Down” buttons.

“Man. Def” (Manual Defrost)
Button Function

This will immediately START a manual defrost
cycle if in refrigeration mode. If already in a defrost
cycle, this will stop the defrost cycle if pushed a
second time. This will not affect or override any
normal defrost programming.
TESTING NOTE: The defrost cycle will not start if
the EVAP sensor temperature is at a temperature
higher than that of the Defrost Termination Set point
(55ºF). The evaporator must be at a colder
temperature.
Push and hold button for at least 5 seconds to
activate. Do not push this button on and off without
waiting at least 5 seconds between periods.

Loss of Power

In event of loss of power, all programmed settings
will remain as those at time of power loss. Clock
time will remain at time of power loss (similar to

* CAUTION: “Cut-Out” = “Cut-In” - “Diff”
Increasing this factory difº value will result in longer compressor running times and colder room temperature. Decreasing this factory difº value

will result in short compressor running on/off cycles.

a conventional defrost clock). When power is
restored, wait at least 15 seconds for display to
indicate the Zone temperature (default display)

Restore Original Factory Default
Settings

To restore unit to original factory default settings:
- Push “Up” and “Down” buttons simultaneously
and hold for at least 5 seconds until display “Ed”
steadily appears (1 second).
- Release Buttons.
The clock is now programmed for factory settings
on Electric Defrost mode.

For Air Defrost (Ad):
- Push “Up” and “Down” buttons simultaneously
and hold for at least 10 seconds until display “Ad”
appears (after “Ed” disappears).
- Release Buttons.
The clock is now programmed for factory settings
on Air Defrost mode.

Function

Display

Adjustment

Factory Default

Shows:

Range:

Setting:

Temp (zone) set point cut -in

“SPº / -10ºF”

-40 to 99ºF

-10ºF

Temp (zone) set point differential*

“difº / 04ºF”

2 to 25ºF

4ºF*

Temp (evap) actual temperature

“Evap” / actual ºF

NA

NA

Fan delay temp (fans cut-in) set point

“Fdº / 25ºF”

15 to 30ºF

25ºF

Defrost termination temp cut -in set point

“dtº / 55ºF”

40 to 70ºF

55ºF

- 2 -