Ad-sp, Air dryer troubleshooting chart (continued) – Bendix Commercial Vehicle Systems AD-SP SYSTEM PURGE AIR DRYER 10/04 User Manual

Page 17

Advertising
background image

17

1. Test fittings, hoses, lines and connections. Apply

soap solution to detect excessive leakage.
Tighten or replace as needed then repeat the air
dryer charge-purge cycle and observe the gauge
installed in the supply reservoir. If leakage is
within limits remove gauge from reservoir and
replace drain cock or valve. If excessive leakage
is detected, continue testing.

2. Test accessories connected to supply reservoir.

Drain all air pressure from system, disconnect all
air lines leading to accessories (fan clutch,
wipers, air seats, etc.) and plug the reservoir at
disconnection point. Build air system pressure
until air dryer purges and observe supply
reservoir gauge. If leakage is no longer
excessive, repair or replace leaking accessory. If
excessive leakage is detected, continue testing.

3. Test governor leakage. Build system pressure to

governor cut-out, turn off engine and apply soap
solution to governor exhaust port and around
cap. Leakage should not exceed a 1" bubble in 5
seconds. Reduce system pressure to 80 psi or
less, and re-apply soap solution. Leakage should
not exceed a 1" bubble in 5 seconds. If
excessive leakage is detected in either test,
repair or replace governor.

4. Test compressor unloader leakage. Drain all air

pressure from system and remove the governor
from the compressor. Temporarily plug the
governor unloader port or air line that mated with,
or connected to, the compressor. Build air
system pressure until air dryer purges then
IMMEDIATELY SHUT OFF THE ENGINE.
Observe the air gauge in the supply reservoir. If
leakage is within limits, replace the compressor
unloaders. Re-connect the governor to the
compressor (after removing plug installed in
governor) and retest while observing supply
reservoir gauge. If excessive leakage is detected,
continue testing.

5. Test air dryer purge valve and outlet (delivery)

check valve. Drain all air pressure from system,
remove the control line connection at the air
dryer and plug the end of the air line leading to
the governor (not the air dryer control port). Build
system pressure to governor cut-out and observe
air gauge. If little or no pressure drop is observed
replace the air dryer check valve. If pressure drop
continues, apply soap solution to air dryer purge
exhaust and purge control port (where the control
line was removed). Leakage should not exceed a
1" bubble in 5 seconds. If leakage is excessive
repair or replace purge valve assembly.

AD-SP

AIR DRYER TROUBLESHOOTING CHART (Continued)

SYMPTOMS

CAUSE

REMEDY

Advertising