46 • Cage and Blade Installation

ClearCube Product Manual and Installation Guide

4. Pull the rack bracket forward and insert the front rack ears on the back bracket

into holes on the front side of the front post. Push forward on the ears until the

latch snaps and locks into place. Ensure the front ears are placed into the

corresponding holes as the back ears, so that the rack bracket is level. To

remove, pull the finger tab inward with your finger and slide the ears forward.

5. Repeat steps 2 and 3 with the other cage bracket on the opposite side of the rack, in

mirrored orientation. Ensure that the brackets are level with respect to each other.

6. Slide the Cage and brackets onto the rack brackets from the front. Ensure the “U”

channels on the cage bracket engage the flanges on the rack bracket.

7. Slide the Cage all the way onto the rack brackets until flush with the front of the rack.
8. Fully tighten the thumb screws with a Phillips head screwdriver.
9. Attach the AC power cord(s) packaged and supplied with the Cage/BackPack and

route it to the rear panel power connector(s) and then to a surge-protected power

source such as an uninterruptible power supply. Use the cable retention clamp on

the Cage to avoid inadvertently disconnecting the power.

The cabling and module installation notes from the previous section, Standard Cage

Mounting Hardware, apply to this procedure.

Chassis Power Requirements

The R4300 Chassis has two internal Power Supply Units (PSUs) and two power

receptacles that provide independent power sources when plugged into separate

circuits.

If only one power cord is connected to the R4300 Chassis, the BackPack is powered

only by a single circuit, although both PSUs are active and supply power to the

BackPack. In order to have redundant AC inputs, and provide the Chassis with the

greatest reliability, each power input must be connected to a separate power source.

The Direct Connect and Switching BackPacks have a single power cord that feeds

both internal PSUs.

Figure 18 Rack Bracket Attachment Points

Back of Rack Bracket

Front of Rack Bracket