Home standby - 40 operating data – Bryant HOME STANDBY ASPAS1BBL040 User Manual

Page 3

Advertising
background image

Home Standby - 40

OPERATING DATA

STANDBY

Home Standby-40

Rated

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

NG / LP

Amp

120/240V, 1-phase, 1.0 pf

37 / 40

154.2 NG / 166.6 LP

MOTOR STARTING

Maximum at 35% instantaneous voltage dip

55 KVA NG / 60 KVA LP

Main Line Circut Breaker

200 Amp

FUEL

NG

LP

Fuel consumption – 60 Hz – 100% Load

ft.

3

/ hr.

570

216

(gal. / hr.)

NA

5.9

m

3

/ hr.

16.1

6.1

COOLING

Coolant capacity

System lit. (US gal.)

21.2 (5.6)

Coolant flow/min.

60 Hz lit. (US gal.)

80.6 (21.3)

Heat rejection to coolant

60 Hz BTU/hr.

161,500

166,700

Radiator air flow

60 Hz m

3

/min. (cfm)

272 (9600)

Maximum operating air temp. onto radiator

°F

140

Maximum operating ambient temp.

°F

120

COMBUSTION AIR REQUIREMENTS

NG

LP

Flow at rated power 60 Hz

m

3

/min. (cfm)

3.3 (115)

3.5 (123)

EXHAUST

NG

LP

Exhaust flow at rated output 60 Hz m

3

/min.(cfm)

11.5 (405)

12.3 (435)

Max. recommended back pressure

Kpa (Hg)

5.0 (1.5)

Exhaust temp. at rated output

°C (°F)

718 (1325)

732 (1350)

Exhaust outlet size

N.P.T. (female)

1.5”

ENGINE

NG

LP

Rated at RPM

60 Hz

1800

HP at rated kW

60 Hz

60.1

64.6

Piston speed

60 Hz m/min. (ft./min.)

331 (993)

BMEP (PSI)

60 Hz

111.1

119.4

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

Temperature

-1.65% for every 12°C above - °C

25

-1.65% for every 10°F above - °F

77

Altitude

-3.0% for every 305 m above - m

183

-3.0% for every 1000 ft. above - ft.

600

TRANSFER SWITCH SPECIFICATIONS

No. of Poles

2

Current Rating

(amps)

200

Voltage Rating

(VAC)

250

Service Disconnect Breaker

200 Amp HACR Type

Utility Voltage Monitor

(fixed)

Pick-up

80%

Drop out

60%

Return to Utility

1 minute

Exercise cycle 15 minutes weekly

Standard

Enclosure - NEMA 3R (Outdoor rated)

Standard

UL Listed

Standard

Dimensions

(H” x W” x D”)

23.5 x 13.05 x 7.4

Weight

(lbs.)

35