Banner SureCross DX80 Wireless Networks User Manual

Page 7

Advertising
background image

Radio and General

Link Timeout

Gateway: Configurable
Node: Defined by Gateway

Radio range is with the 2 dB antenna that ships with the product.
High-gain antennas are available, but the range depends on the
environment and line of sight. To determine the range of your wire-
less network, perform a Site Survey.

Wiring Access

Four PG-7, One 1/2-inch NPT, One 5-pin Euro-style
male connector

For European applications, power the DX80 from a Limited Power
Source as defined in EN 60950-1.

Inputs and Outputs

Discrete Inputs

Rating: 3 mA max current at 30V dc
Sample Rate: 62.5 milliseconds
Report Rate: On change of state

Discrete Input ON Condition

PNP: Greater than 8V
NPN: Less than 0.7V

Discrete Input OFF Condition

PNP: Less than 5V
NPN: Greater than 2V or open

Analog Inputs

Rating: 10V
Impedance: 100 Ohms
Sample Rate: 62.5 milliseconds
Report Rate: 1 second or On Change of State (1%
change in value)
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit

Discrete Outputs

Update Rate: 125 milliseconds
ON Condition: Supply minus 2V
OFF Condition: Less than 2V
Output State Following Timeout: OFF

Discrete Output Rating (PNP)

100 mA max current at 30V dc
ON-State Saturation: Less than 3V at 100 mA
OFF-state Leakage: Less than 10 μA

Analog Outputs

Update Rate: 125 milliseconds
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit

To verify the analog input's impedance, use an Ohm meter to
measure the resistance between the analog input terminal (AIx)
and the ground (GND) terminal.

Environmental and Certifications

Ratings

DX80 models:IEC IP67; NEMA 6; (See UL section be-
low for any applicable UL specifications)
DX80...C models: IEC IP20; NEMA 1 (In a suitable en-
closure: Class I, Division 2, Group A, B, C, D; T4 −40
to 80 °C)

Conditions

Operating Temperature: −40 to +85 °C (Electronics);
−20 to +80 °C (LCD)
Operating Humidity: 95% max. relative (non-condens-
ing)
Radiated Immunity: 10 V/m, 80-2700 MHz
(EN61000-6-2)

Shock and Vibration

IEC 68-2-6 and IEC 68-2-7
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz

Refer to the

SureCross DX80 Wireless I/O Network Product Man-

ual

(p/n 132607) for installation and waterproofing instructions. Op-

erating the devices at the maximum operating conditions for exten-
ded periods can shorten the life of the device.

DX8x...C (External Wiring Terminal Models)

CSA: Class I, Division 2, Groups A, B, C, D

(Ex/A Ex nA II T4); Certificate: 1921239

LCIE/ATEX: Zone 2 (II 3G / Ex nA IIC); Certifi-

cate: LCIE 10 ATEX 1012 X

UL Listing

Maximum ambient temperature: 70 °C
Mounting instructions: See document 132607
Power rating: 10 to 30V dc, UL Class 2
Enclosure environmental rating: UL Type 1

SureCross DX80 Node

P/N 134323 Rev. G

www.bannerengineering.com - tel: 763-544-3164

7