Switches

Device Settings

1

2

3

4

5

6

7

8

Low resolution (1 degree)

ON

Discrete sinking inputs

OFF*

Discrete sourcing inputs

ON

Thermocouple, J-Type

OFF*

OFF*

OFF*

OFF*

Thermocouple, B-Type

OFF

OFF

OFF

ON

Thermocouple, C-Type

OFF

OFF

ON

OFF

Thermocouple, D-Type

OFF

OFF

ON

ON

Thermocouple, E-Type

OFF

ON

OFF

OFF

Thermocouple, G-Type

OFF

ON

OFF

ON

Thermocouple, K-Type

OFF

ON

ON

OFF

Thermocouple, L-Type

OFF

ON

ON

ON

Thermocouple, M-Type

ON

OFF

OFF

OFF

Thermocouple, N-Type

ON

OFF

OFF

ON

Thermocouple, P-Type

ON

OFF

ON

OFF

Thermocouple, R-Type

ON

OFF

ON

ON

Thermocouple, S-Type

ON

ON

OFF

OFF

Thermocouple, T-Type

ON

ON

OFF

ON

Thermocouple, U-Type

ON

ON

ON

OFF

Modbus or UCT configured (overrides DIP
switches)

ON

ON

ON

ON

* Default configuration
** In high resolution mode, the temperature = (Modbus register value) ÷ 20. In low resolution mode, the temperature = (Modbus register
value) ÷ 2.
Address Mode
The SureCross wireless devices may use one of two types of addressing modes: rotary dial addressing or extended addressing. In
rotary dial address mode, the left rotary dial establishes the network ID and the right rotary dial sets the device ID. The wireless network
is restricted to a maximum of 16 devices.
Extended address mode uses a security code to "bind" Nodes to a specific Gateway. Bound Nodes can only send and receive informa-
tion from the Gateway to which they are bound. In extended address mode, wireless networks may contain up to 48 radio devices. For
more information on extended address mode, refer to the SureCross™ Wireless I/O Network product manual.
The device ships in rotary dial address mode by default, with the DIP switch in the OFF position. To use extended address mode, change
the DIP switch to the ON position.
Discrete Input Type
Select the type of discrete input sensors to use with this device: sourcing (PNP) sensors or sinking (NPN) sensors.
Modbus/User Configuration Tool (UCT) or DIP Switch Configured
In Modbus/UCT Configured mode, the device parameters are changed using the User Configuration Tool (UCT) or a Modbus command.
All DIP switch positions are ignored. In DIP Switch Configured mode, use the DIP switches to configure the parameters listed in the table.

SureCross DX80 FlexPower Thermocouple Node

P/N 131297 Rev. I

www.bannerengineering.com - tel: 763-544-3164