Setting up your wireless network – Banner SureCross DX80 Wireless Networks User Manual

Page 2

Advertising
background image

Setting Up Your Wireless Network

To set up and install your wireless network, follow these steps:

1. Configure the DIP switches of all devices.
2. Connect the sensors to the SureCross devices.
3. Apply power to all devices.
4. Form the wireless network by binding the Nodes to the Gateway. If the binding instructions are not included in the datasheet, refer to

the product manual for binding instructions.

5. Observe the LED behavior to verify the devices are communicating with each other.
6. Conduct a site survey between the Gateway and Nodes. If the site survey instructions are not included in this datasheet, refer to the

product manual for detailed site survey instructions.

7. Install your wireless sensor network components. If installation instructions are not included in this datasheet, refer to the product

manual for detailed installation instructions.

For additional information, including installation and setup, weatherproofing, device menu maps, troubleshooting, and a list of accesso-
ries, refer to one of the following product manuals.

SureCross Quick Start Guide: Banner part number

128185

• SureCross Wireless I/O Network Manual:

132607

• Web Configurator Manual (used with "Pro" and DX83 models):

134421

Host Configuration Manual

132114

Configuring the DIP Switches

Before making any changes to the DIP switch positions, disconnect the power. DIP switch changes will not be recognized if power isn't
cycled to the device.
For parameters not set via DIP switches, use the User Configuration Tool (UCT) to make configuration changes. For parameters set
using the DIP switches, the DIP switch positions override any changes made using the User Configuration Tool.

DIP Switch Settings

Switches

Device Settings

1

2

5

6

7

8

Rotary switch address mode

OFF*

Extended address mode

ON

Modbus or UCT configured (overrides switches
3-8)

OFF*

DIP switch configured

ON

Discrete IN #1 Sinking (NPN)

OFF*

Discrete IN #1 Sourcing (PNP)

ON

Discrete IN #2 Sinking (NPN)

OFF*

Discrete IN #2 Sourcing (PNP)

ON

Counter 2: rate (frequency) counter

OFF*

Counter 2: event counter

ON

Report Rate 16 seconds

OFF*

Report Rate 1 second

ON

* Default configuration

SureCross DX80 FlexPower Counter Node

2

www.bannerengineering.com - tel: 763-544-3164

P/N 136348 Rev. G

Advertising