Teaching limits using the auto-window feature – Banner U-GAGE QT50U Ultrasonic Sensors User Manual

Page 5

Advertising
background image

Action

Result

Position the target for the second limit.

Click the TEACH button.

The sensor stores both limits and Output LED turns solid amber.

The sensor returns to Run mode.

Pump-In Application

(using Normally Open Output)

Pump-Out Application

(using Normally Closed Output)

Initial Tank Level -

Outputs are INACTIVE

Level Drops Below Far Limit -

Outputs ACTIVATE

Level Rises Above Near Limit -

Outputs DEACTIVATE

1

Flow

Flow

Initial Tank Level -

Outputs are INACTIVE

Level Rises Above Near Limit -

Outputs ACTIVATE

Level Drops Below Far Limit -

Outputs DEACTIVATE

Pump Control

Pump Control

Level Rises Above Near Limit -

Output DEACTIVATES

Level Rises Above Near Limit -

Outputs DEACTIVATE

Initial Tank Level -

Output is INACTIVE

Level Rises Above Near Limit -

Outputs DEACTIVATE

Level Drops Below Far Limit -

Output ACTIVATES

Initial Tank Level -

Outputs are INACTIVE

Level Drops Below Far Limit -

Outputs ACTIVATE

Level Rises Above Near Limit -

Outputs DEACTIVATE

Level Rises Above Near Limit -

Output ACTIVATES

Level Rises Above Near Limit -

Outputs DEACTIVATE

Initial Tank Level -

Output is ACTIVE

Level Rises Above Near Limit -

Outputs DEACTIVATE

Level Drops Below Far Limit -

Output DEACTIVATES

Figure 5. Fill-Level Control

The Fill-Level Control mode provides the switching logic required for fill-level, web tensioning control, and similar

applications. In this mode, the output energizes when the target reaches the first sensing window limit, and stays

energized until the target moves to the second limit. The output then de-energizes at the second limit and does not re-

energize until the target moves, again, to the first limit.

Teaching Limits Using the Auto-Window Feature

Output OFF

Output ON

Output OFF

Position

+ 100 mm

Position

- 100 mm

Taught Position

Output ON

Output ON

Output OFF

Position

+ 100 mm

Position

- 100 mm

Taught Position

Normally Closed Output

Normally Open Output

Figure 6. Using the Auto-Window feature for programming

Teach procedures are identical for window-limit and fill-

level control models. Teaching the same limit twice

automatically centers a 200 mm window on the taught

position. To readjust the sensing midpoint, repeat the teach

procedure.

A button click is defined as: 0.04 s. ≤ Click ≤ 0.8 s.

1. Enter programming mode.

Action

Result

Push and hold TEACH push button for 2 seconds.

Output LED turns solid red and the sensor waits for first limit.

2. Teach the first limit.

U-GAGE QT50UVR Series Sensors

P/N 117764 Rev. F

www.bannerengineering.com - tel: 763-544-3164

5

Advertising