Installation Instructions

Series 007 and LF007

1

2

" - 2" (15 - 50mm)

Service and Maintenance

Servicing the First and Second Check Valves

NOTICE

Before servicing, ensure supply water is turned off or shutoff valves

are in the closed position.

1. Remove the cover, then remove the retainer from the body

valve. The check valve modules can now be removed from the

valve by hand or with a screwdriver.

NOTICE

For Series 007 and LF007 sizes

1

2

" - 2" (15-50mm), the seats and

springs of the first and second check modules are not interchange-

able. The heavier spring and smaller diameter seat belong with the

first check module. Series 007M1 sizes

3

4

" - 1" (20-25mm) and

Series 007M2

3

4

" (20mm) have interchangeable seats and springs.

2. The check seats are attached to the cage with a bayonet type lock-

ing arrangement. Holding the cage in one hand, push the seat in-

ward and rotate clockwise against the cage. For

3

4

" (20mm) Series

007M2/LF007M2 and LF007 pull apart seat and cage. The seat,

cage, spring and disc assembly are now individual components.

3. The disc assembly may now be cleaned and reassembled or,

depending on its condition, it may be discarded and replace with

a new assembly from the repair kit. O-rings should be cleaned or

replaced as necessary.

4. Reassemble the check valve module in the reverse order. Check

modules are installed in the valve body with the seats facing the

valve inlet. The modules must be securely in place before the

retainer can be replaced. On the

3

4

" - 1" (20-25mm)size, this

retainer may have to be tilted slightly into place. Replace cover.

First

Shutoff Valve

Strainer

007QT-S / LF007QT-S

WattsBox Insulated

Enclosure

Available in Aluminum

or Fiberglass.

For more information,

send for ES-WB.

First

Shutoff Valve

First Shutoff Valve

Figure 1

Figure 2

Figure 3

First Shutoff

Valve

007QT-S/LF007QT-S
Vertical flow-up installation

Strainer

007QT-S / LF007QT-S

Cover

Cover

O-ring

Retainer

Body

First Check

Second Check

Seat

Seat

O-ring

Disc

Assembly

Spring

Check

Cage

O-rings

Check

Cage

Spring

Disc

Seat

Cover

Cover

O-ring

Retainer

Body

Second Check

First Check

Parallel -

Figure 3

Two or more Series 007 and LF007 smaller size valves may be

piped in parallel (where approved) to serve a larger supply pipe

main. This type of installation is employed whenever it is vital to

maintain a continuous supply of water/where interruptions for test-

ing and servicing would be unacceptable. It also has the advantage

of providing increased capacity where needed beyond that provided

by a single valve and permits testing or servicing of an individual

valve without shutting down the

complete line.
For two valve installations the total capacity of the devices should

equal or exceed that required by the system.
The quantity of valves used in parallel should be determined by

the engineers judgement based on the operating conditions of a

specific installation.

2

For repair kits and parts, refer to our Backflow

Prevention Products Repair Kits & Service Parts

price list PL-RP-BPD found on

www.watts.com.