Watts M1116-52 User Manual

Mustang series, Pressure relief and surge anticipator valve

Advertising
background image

8550 Hansen Road

Houston, Texas 77075

(Ph) 713.943.0688

(Fx) 713.944.9445

www.wattsacv.com

01/05

R

Mustang Series

M116-52 or M6116-52 (Globe)

M1116-52 or M61116-52 (Angle)

Specifications

The Combination Surge Anticipator and Pressure Relief Control Valve shall be a pilot operated diaphragm
valve designed to minimize the effects of water hammer and pressure surges resulting from: 1) Normal
pump starting and stopping operations or 2) Mechanical or electrical power failure situations. The valve
shall sense hydraulic pressure changes above and below the adjustable setpoints of the pilot control system
directly from the pump station discharge header.

The main valve shall be a hydraulically operated, single diaphragm actuated, globe or angle pattern valve.
Y-pattern valves shall not be permitted. The valve shall contain a disc and diaphragm assembly that forms
a sealed chamber below the valve cover, separating operating pressure from line pressure. The diaphragm
shall be constructed of nylon reinforced Buna-N, and shall not seal directly against the valve seat and shall
be fully supported by the valve body and cover. Rolling diaphragm construction will not be allowed and there
shall be no pistons operating the main valve or any pilot controls.

The main valve body and cover shall be Ductile Iron ASTM A536, and all internal cast components shall
be Ductile Iron or CF8M (316) Stainless Steel. All Ductile Iron components, including the body and cover,
shall be lined and coated with an NSF 61 Certified Epoxy Coating applied by the electrostatic heat fusion
process. All main valve trim and throttling components (cover bearing, valve seat and disc guide) shall
be Stainless Steel. The valve body and cover must be machined with a 360-degree locating lip to assure
proper alignment.

The disc and diaphragm assembly shall contain a Buna-N synthetic rubber disc with a rectangular cross-
section that is securely retained on 3-1/2 sides by a disc retainer and disc guide. Diaphragm assemblies
utilizing bolts or cap screws for component retention will not be permitted.

The exposed portion of the seat disc shall contact the valve seat and seal drip-tight. The disc and diaphragm
assembly must be guided by two separate bearings, one installed in the valve cover and one concentrically
located within the valve seat, to avoid deflection and assure positive disc-to-seat contact. Center guided
valves will not be permitted. All necessary repairs shall be made from the top of the valve while the body
remains in line.

The pilot control system shall contain an external Y-Strainer, Adjustable Opening and Closing Speed,
Low Pressure Opening Pilot with Test Valves and Pressure Gauge, High Pressure Relief Pilot, Hydraulic
Accumulator with Drain Pilot, Valve Position Indicator and Isolation Ball Valves on all body connections. The
pilot control system shall utilize copper tubing and brass fittings. The adjustment range of the high-pressure
relief pilot shall be 20-200 psi and the low pressure opening pilot shall be 20-175 psi.

The valve shall be Watts ACV Model M116-52 or M6116-52 (globe) or M1116-52 or M61116-52 (angle)
pattern Combination Surge Anticipator and Pressure Relief Control Valve.

PRESSURE RELIEF and
SURGE ANTICIPATOR VALVE

Advertising
This manual is related to the following products: