Watts R13-1200 User Manual

Page 9

Advertising
background image

III. OPERATION

A. INSTALLATION

1.

Proper pretreatment must be determined and installed prior to the RO system.

2.

The water supply and pretreatment equipment should be sufficient to provide a
minimum of 10-psig at the maximum feed flow.

3.

An electrical receptacle with a ground fault interrupt (GFI) is highly recommended.

4.

Responsibility for meeting local electrical and plumbing codes lies with the owner /
operator.

5.

Install indoors in an area protected from freezing. Space allowances for the removal
of the membranes from the pressure vessels should be provided.

6.

The prefilter housing and membrane housings are usually removed for shipment. The
RO membrane housing(s) can be identified by the fitting installed in the bottom. The
prefilter housing does not have a fitting in the bottom.

7.

Install the prefilter housing with its cartridge (see figure #1, item I).

8. Install

the

RO

membrane

housing(s) with the membrane(s) (see figure #1, item K).

9.

Connect the tubing to the bottom of the RO membrane housing(s). On system with
one membrane the tubing connects from the bottom of the membrane housing to the
reject valve assembly. On system with two membranes, one piece of tubing connects
from the bottom of the left membrane to the inlet (upper right) of the right membrane.
A second piece of tubing connects the bottom of the right membrane to the reject
valve assembly. The fittings are tagged to indicate the proper tubing connections.


B. PLUMBING CONNECTIONS

Note: It is the responsibility of the end user to ensure that the installation is done according to
local codes and regulations.

1.

Connect the pretreated feed water line to the prefilter inlet (Figure # 1 item M). A
feed water shutoff valve should be located within 10 feet of the system.

2.

Temporarily connect the product water outlet to a drain. The product outlet is located
behind the panel at the top of the product flow meter. The product water line should
never be restricted. Membrane and/or system damage may occur if the product line is
blocked.

3.

Connect the reject water outlet to a drain. The reject outlet is located behind the
panel at the top of the reject flow meter. The reject drain line should never be
restricted. Membrane and/or system damage may occur if the reject drain line is
blocked. An air gap must be located between the end of the drain line and the drain.
The use of a standpipe or other open drain satisfies most state and local codes and
allows for visual inspection and sampling.



Advertising
This manual is related to the following products: