Hot Water Temperature Control Valves

Sizes:

1

2

" – 1" (15 – 25mm)

Series 1170, L1170 Hot Water Temperature Control Valves are spe-

cifically designed for mixing hot and cold water on hot water supply

systems. They can be used for a variety of applications to reduce the

temperature of the hot water from the system, and are ideal for radi-

ant heat applications. This series features a “double throttling” design

which combines the control of the hot and cold water to provide a

sensitive response to changes in water temperature passing through

the mixing chamber.
The 1170-M2 can be set to any temperature between 90°F and

160°F (60°F and 120°F for model L1170-M2) with flow rates as low

as 0.5 gpm and as high as 23 gpm (refer to capacity chart on the

back). The superior flow characteristics of this valve provide accu-

rate temperature control to the requirements of ASSE 1017* across

the rated flow range.
These valves also provide additional safety as they restrict mixed

water out to a drip upon loss of cold water supply to the valve.
As an added feature, the 1170-M2 and L1170-M2 incorporate integral

check valves and filter washers in both the hot and cold water inlets to

protect against cross flow. Available with threaded (-UT), solder (-US),

PEx, (-QC) Quick-Connect or CPVC connections.

Features

• Bronze body construction
• Solid wax hydraulic principle thermostat assures dependable

mixing of hot and cold water

• Thermostat controls both hot and cold water
• Models available with solder, thread, PEx, Quick-Connect or

CPVC end connections

• Integral filter washers and check valves
• Adjustment cap with locking feature
• ASSE 1017 listed*

Specifications

A Hot Water Temperature Control Valve shall be installed on water

heating equipment to provide tempered water to supply piping.

Valve shall have a bronze body, include integral check valves and

operate so the thermostat controls the cold and hot water ports.

The valve shall be provided with solder (-US), threaded (-UT), PEx,

(-QC) Quick-Connect or CPVC connections. Valve shall be ASSE

Standard 1017* Listed. Valve shall be a Watts Regulator Company

1170-M2 or L1170-M2.

*ASSE 1017 listing is for valves used in hot water source applications.

1170-US-M2

Minimum flow requirements to maintain

set temperature for Series 1170-M2

ValVe Size

gpm

1

2

" – 1"

.5

ASSE Standard 1017 Listed*

†WARNING

Watts Hot Water Temperature Control Valve Series 1170 are designed to be installed

at or near the boiler or water heater. They cannot be used by themselves for temper-

ing water temperatures at fixtures where ASSE Standard 1016 or ASSE Standard

1070 listed devices are required. To comply with ASSE Standard 1016 or ASSE

Standard 1070, listed devices such as Watts Series L111, USG or MMV should be

used at fixtures to prevent possible injury.
Watts Hot Water Temperature Control Valve Series 1170 are not designed to com-

pensate for system pressure fluctuations. Such use may result in severe bodily injury

(i. e. scalding or chilling) and/or death.
When installing the Series 1170 valves in radiant heat applications, the components

of the radiant heat system must be of materials with a construction capable of with-

standing the high limit output temperatures of the heating boiler. If you are uncertain

as to the product’s adaptability for your application, please consult an authorized

representative before installing or using the product.

1170-QC-M2

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.