Watts 6115-JM User Manual

Technical bulletin

Advertising
background image

8550 Hansen Road . Houston, TX 77075 . Telephone 713.943.0688 . FAX 713.944.9445 www.wattsacv.com

Technical Bulletin

Technical Bulletin

Pressure Reducing Control Valve

Pressure Reducing Control Valve

The Automatic Answer to Fluid Control

Model 6115-JM

Part Number List

Item Description

Complete Assembly

Repair Kit

Model 6115-JM

234801

3313-01

Reducing Pilot

0661-01

221101

Operation

The Model 6115-JM is designed to automatically reduce a fluctuating higher upstream (inlet) pressure to a constant
lower downstream (outlet) pressure. It is controlled by a normally open Pressure Reducing Pilot Regulator designed
to: 1) Open (allowing fluid out of the main valve cover chamber) when downstream pressure is below its adjustable
setpoint, and, 2) Close (allowing fluid to fill the main valve cover chamber) when downstream pressure is above its
adjustable setpoint. A decrease in downstream pressure causes the valve to modulate towards an open position,
raising downstream pressure. An increase in downstream pressure causes the valve to modulate towards a closed
position, lowering downstream pressure.

Standard Components

1) Main Valve
2) Reducing Pilot
3) Supply Orifice
4) Adjustable Opening Speed
5) Position Indicator
6) Flow Clean Strainer
7) Ball Valve

Closes Valve

Opens Valve

1

2

3

4

5

Flow

Flow Direction: Under the Seat

6

7

Advertising