Series N170

Hot Water Master Tempering Valves

Watts Series N170 hot water master tempering valves are

especially designed for use on larger hot water supply systems

for mixing hot and cold water for a variety of applications to

extend the hot water supply. This series uses paraffin-based

thermostat to sense and adjust outlet temperature.

Features

• ASSE 1017 and IAPMO

C

UPC Listed

• N170-M3 uses paraffin-based thermostat to sense and

adjust outlet temperature

• Dirt and lime resistant poppet and seat design
• Virtual shutoff if supply pressure fails
• Vandal-resistant locking mechanism to secure temperature

setting

• Factory tested

Specifications

Maximum Operating Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125psig (861 kPa)
Maximum Hot Water Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . 200°F (93°C)
Minimum Hot Water Supply Temperature . . . . . . . . . . . . . . . . . . . . . 5°F (3°C) Above Set Point*
Temperature Adjustment Range** . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 - 180°F (32 - 82°C)
Hot Water Inlet Temperature Range . . . . . . . . . . . . . . . . . . . . . . . . . 120 - 180°F (42 - 82°C)
Cold Water Inlet Temperature Range . . . . . . . . . . . . . . . . . . . . . . . . 40 - 80°F (4 - 27°C)
Listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASSE 1017, IAPMO

C

UPC

Approval Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ASSE 1017, CSA B125.3


*With Equal Pressure
**Low Limit cannot be less than the cold water temperature. For best operation, hot water should be at least 5°F (3°C) above desired set point.

For Commercial Applications

ES-N170-M3

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

N170-M3

N170-M3 CSUT

Watts Hot Water Master Tempering Valves cannot be used for

tempering water temperature at fixtures. Severe bodily injury (i.e.,

scalding or chilling) and/or death may result depending upon system

water pressure changes and/or supply water temperature changes.

ASSE standard 1016, 1069 or 1070 listed devices such as Watts

Series MMV, USG, and L111 valves should be used at fixtures to

prevent possible injury.
The Watts Hot Water Tempering Valves are designed to be installed at

or near the boiler or water heater. They are not designed to compensate

for system pressure fluctuations and should not be used where ASSE

standard 1016, 1069 or 1070 devices are required. These Watts valves

should never be used to provide “anti-scald” or “anti-chill” service.