Watts CSM-61-T User Manual

Watts series csm-61(threaded) & lfcsm-61(solder), Flow measurement/balancing valves, Pressure - temperature limits

Advertising
background image

Memory

Screw

Figure 1

Pressure - Temperature Limits

Pattern

Type of Solder

Working Temp.

Maximum Pressure

°F

°C

psi

bar

Solder-to-Solder

95.5

200

93

125

8.6

(Lead Free)

(Tin-Antimony)

Thread-to-Thread

250

121

300

20.7

Installation

1. Install valve on return line of equipment to be balanced or as

shown on the plans.

2. For maximum accuracy, the flow measurement valve should

be located in an unrestricted straight pipe run so that no fit-

tings (elbow, valve, tee, etc.) is closer to the measurement

valve than 5 pipe diameters upstream and 2 pipe diameter

downstream. If a balancing valve is located downsteam from

a circulation pump, allow a distance of ten (10) diameters

between the pump and balancing valves.

3. Series CSM-61M1 and LFCSM-61M1 flow measurement

valves are bidirectional and should be installed to insure ease

of hooking up meter, adjusting setting and enabling memory

device. A

1

8

" (3 mm) NPT plugged port is installed on each

measurement valve and can be used as a drain port if needed.

4. Solder end valves are designed to be soft soldered into lines

without disassembly, using a low temperature solder (400°F)

(204°C). Other solders such as 95/5 tin antimony (460°F)

(238°C) can be used, however, extreme caution must be

used to prevent seat damage. Higher temperature solders will

damage the seat material.

5. Apply heat with flame directed away from the center of the

valve body. Excessive heat can harm the seats.

6. Heat solder joints only to the point were solder will flow prop-

erly. Excessive heat may distort brass castings.

Flow Measurement Instruction

1. Loosen memory screw.
2. With wrench, turn indicator to open position on indicator

plate. Do not force past this point.

3. Connect, vent and prepare the differential gauge. Refer to

instructions furnished with the gauge.

4. After initial pressure differential reading is taken, refer to flow

rate charts to obtain flow rate based on pressure differential

and valve setting. If flow rate is in excess of that specified,

turn indicator towards closed position, noting pressure drop

and valve setting and determining new flow rates from flow

rate chart. Once correct flow rate setting has been estab-

lished, slide memory stop clockwise towards open side of

indicator plate until memory stop ring hits indicator plate. Do

not force beyond this point. Tighten memory screw. Refer to

Figure 1. The unit or system has now been balanced and the

memory set.

5. After memory is set, disconnect differential gauge.

Watts Series CSM-61(Threaded)
& LFCSM-61(Solder)

Flow Measurement/Balancing Valves

Sizes: 1

1

4

", 1

1

2

", 2", 2

1

2

", and 3"

IS-CSM-61-L

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information

can result in death, serious personal injury, property

damage, or damage to the equipment.
Keep this Manual for future reference.

Use caution when soldering. Protect yourself and others.

FUMES AND GASES can be hazardous to your health. HEAT

RAYS (INFRARED RADIATION) from flame or hot metal can

injure eyes.

Watts Flow Measurement/Balancing Valves are available in the

straightway pattern with threaded or solder end connections.

All tapered pipe threads conform to FEDERAL SPECS H28.

Valves conform to ANSI B16.18 and ANSI B16.22.
Maximum Pressure/Temperature Ratings: 300psi (20.7 bar) - 250°F

(121°C).