Materials

Springs:

Stainless steel

Bonnet:

PPO

Vent Disc:

EPDM

Disc Holder: PPO
Check Disc: Silicone rubber
Body:

Lead Free* cast copper silicon alloy

Pressure – Temperature

Temperature Range: 33°F – 180°F (0.5°C – 83°C)
Maximum Working Pressure: 150psi (10.3 bar)

End Connections

Female NPT - Ball Valve shutoffs

Capacity

As compiled from documented Foundation for Cross-Connection

Control and Hydraulic Research at the University of Southern

California lab tests.

==

Typical maximum system flow rate (7.5 feet/sec.)

A strainer is recommended to be installed ahead of the backflow preventer to prevent the fouling of the check assembly
and resulting spillage from the valve during repressurization. Do not install in concealed locations or areas where water
leakage due to normal wear of the internal parts can cause damage.

Standards

Meets requirements of IAPMO.

Approvals

D

E

2"

B

kPa psi

69 10

55 8

41 6

28 4

14 2

0 0

0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5

gpm

0 1.9 3.8 5.7 7.6 9.5 11.4 13.3 15.2

17.1 19 21

lpm

3

8

" (10mm)

∆P

FLOW

kPa psi

97 14
83 12
69 10
55 8
41 6
28 4
14 2
0 0

0 1 2 3 4 5 6 7 8 9

10

gpm

0 3.8 7.6 11.4 15.2 19 22.8 27 30 34 38

lpm

7.5

fps

2.3

mps

==

∆P

FLOW

3

4

" (20mm)

kPa psi
69 10
55 8

41 6

28 4

14 2
0 0

0 5 10 15 20 25 30

gpm

0 19 38 57 76 95

114

lpm

7.5

fps

2.3

mps

∆P

FLOW

0 5 10 15 20 25 30 35 40 45 50

gpm

0 19 38 57 76 95 114 135 152

171

190

lpm

7.5

fps

2.3

mps

kPa psi
69 10

55 8

41 6

28 4

14 2

0 0

1" (25mm)

∆P

FLOW

Dimensions — Weights

LF008PCQT

SizE (DN)

DimENSiONS

WEigHT

B D E

in. mm in. mm in. mm in. mm lbs. kgs.

3

8

10 5

1

2

140 3

15

16

100 3

1

8

79 1.6 .73

1

2

15 5

3

4

146 4

3

16

106 3

3

8

86 1.7 .77

3

4

20 7 178 4

5

8

117 4

1

2

114 3.8 1.72

1 25 7

1

2

191 5

1

8

130 4

7

8

124 4.8 2.18

1056

B64.1.2

3

4

" (20mm) Hose

Adapter with

strainer washer

Supply Hose

Shutoff

Test cock

Dispensing inducers

Solenoid Valves

LF008PCQT-S Watts P60-m1

Pressure Reducing Valve

Typical Installation

1" min.

(25mm)

ES-LF008PCQT 1318

© 2013 Watts

USA: Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com

Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.watts.ca

A Watts Water Technologies Company

==

==

1

2

" (15mm)

NOTICE

Advertising