Watts flange adapter installation, Pressure - temperature limits, Field conversion – Watts TDV User Manual

Page 2: Flow indicator scale

Advertising
background image

B

A

2

Watts

Flange Adapter Details

125 psi/150 psi

Ductile Iron

Valve

Bolt

Size

No.

Size

2

1

2

4

5

8

3

4

5

8

4

8

5

8

5

8

3

4

6

8

3

4

8

8

3

4

10

12

7

8

12

12

7

8

Watts Flange Adapter Installation

1. Position the two halves of Watts Flange Adapter on the valve

body (Fig. 1) ensuring that the lugs on each half of the flange

adapters are located between the anti-rotation lugs on the

valve body. Insert two bolts of specified size (Table 1) to

secure the halves of the flange adapter to the valve body (Fig.

2). The gasket cavity should face out to the adjoining flange.

2. Lubricate the inner and outer diameter of the gasket with the

lubricant provided or a similar

non-petroleum base water

soluble grease.

3. Press the gasket firmly into the flange cavity ensuring that

the sealing lip is pointed outward. When in place, the gasket

should not extend beyond the end of the pipe (Fig. 3).

4. Position the adjoining flange or the pipe to the Watts Flange

Adapter and install the remaining bolts. The two locking bolts

should be tightened first in order to position the flanges cor-

rectly as shown in Fig. 1.

NOTE: Care should be taken to ensure that the gasket is not

pinched or bent between flanges.

5. Tighten remaining nuts evenly, following bolting instructions

(Fig. 4), so that the flange faces remain parallel. Flange bolts

should be tightened to 70 ft./lbs. torque minimum to assure

firm metal-to-metal contact. When raised face flanges are

used, there will be a gap between the faces of the outer

diameter.

6. Flange gaskets are not interchangeable with other mechanical

pipe couplings or flange gaskets.

Start

1

2

3

4

5

10
11

12

13

6
7

14

15
16

8
9

Table 1

Fig. 4

Pressure - Temperature Limits

-46° -29° -18°

10°

38°

66°

93°

110°

-50° -20° 0°

50°

100°

150°

200° 230°

400

375
300
250
200

100

0

2760

2585
2070
1724
1380

690

250

Temperature °C

Temperature °F

Pressure psi

Pressure kP

a

A

B

Fig. 2

Fig. 3

Fig. 1

Field Conversion

(Straight to Angle pattern valve)

1. Open valve at least one complete turn.
2. Remove the body bolts from valve body using Allen Key
3. Rotate one half of the valve body 180° making sure the lower

valve seat and O-ring stay in position. Inspect the O-ring for

any cuts or nicks and replace if necessary.

4. Replace body bolts and torque evenly to 70 ft./lbs.

Flow Indicator Scale

The valve stem with its grooved rings

and positioning sleeve indicates the

throttled position of the valve. The quar-

ter turn graduations on the sleeve, with

the scribed line on the stem, provide for

approximate flow measurement.
NOTE: The valve is shipped in the

closed position. The indicator on

the plastic sleeve is aligned with the

vertical scribed line on the stem.

Recommended Bolt Tightening Procedure

Legend

Watts Ductile iron flange

adapters for ANSI 150# flanges

Grooved end with 375 psi rated

pipe coupling