Watts LF289 User Manual

Series lf289, Lead free, Spill resistant atmospheric vacuum breakers

Advertising
background image

Series LF289

Spill Resistant

Atmospheric Vacuum Breakers

Sizes:

3

8

"–

3

4

"(10 – 20mm)**

Series LF289 is designed for indoor point of use applications

to prevent backsiphonage of contaminated water back into the

potable water supply. Separation of the water supply from the air

inlet is accomplished by means of a diaphragm seal. This fea-

ture protects against any spillage during start-up operation. The

LF289 features Lead Free* construction to comply with Lead

Free* installation requirements.

Features

• Spring loaded vent
• Spill-resistant diaphragm design for indoor use
• Affordable design
• Modular cartridge for ease of service
• Vent uses an O-ring for reliable operation
• Lead Free* Copper Silicon Alloy
• Compact space saving design
• Meets ASSE 1001 (

3

8

" and

1

2

" only)

• Optional satin chrome finish

Installation

The LF289 is designed to be installed at the point of use. When

factory installed deck/machine mounted on machines or equip-

ment, the critical level of the LF289 shall be 1" (25mm) above the

flood rim. If field applied for general plumbing applications, the

critical level of the LF289 shall be 6" (152mm) above the flood rim.

Specifications

A spill-resistant atmospheric vacuum breaker shall be installed,

in accordance with the manufacturer's instructions, as noted on

the plans. The Lead Free* Atmospheric Vacuum Breaker shall be

constructed using Lead Free* materials. Lead Free atmospheric

vacuum breaker shall comply with state codes and standards

where applicable, requiring reduced lead content. The valve shall

consist of a one piece modular check and float assembly made

of engineered thermoplastic and housed in a Lead Free cast

copper silicon alloy body. Springs shall be stainless steel. The

valve shall be constructed with a molded diaphragm separating

the air inlet from the potable water supply to prevent spillage.

The valve shall be a Watts Series LF289.

Series LF289

Hood

Bonnet

Vent Spring

O-ring

Vent O-ring

Retainer

Body

Hood Screws

(2 Req'd)

Check

Assembly

3

8

"

and

1

2

"

sizes only

1001

Typical Installation

Watts LF289

Flood Rim Level

Supply Line

LF289 to be installed

6"above the flood

rim if field applied

for general plumbing

applications.

For Health Hazard Applications

ES-LF289

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. –––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

LEAD FREE

*

*The wetted surface of this product contacted by consumable

water contains less than 0.25% of lead by weight.

**

Metric Dimensions are nominal pipe diameter. This product is

produced with NPT threaded end connections.